Download Print this page
GE IC695CMM002CA-EJ Important Product Information

GE IC695CMM002CA-EJ Important Product Information

Pacsystems* rx3i serial communications modules

Advertisement

Quick Links

Important Product Information
IC695CMM004-EJ, IC695CMM004CA-EJ, and IC695CMM004LT-EJ
GFK-2461N
April 2018
PACSystems* RX3i Serial Communications modules expand the serial
communications capabilities of the RX3i system.
Serial Communications module IC695CMM002 provides two independent,
isolated serial ports. Serial Communications module IC695CMM004, illustrated at
right, provides four independent, isolated serial ports.
Up to six Serial Communications modules can be located in the main
PACSystems RX3i backplane
The IC695CMM00xCA modules are the conformal-coated versions of the
IC695CMM00x modules.
The IC695CMM004LT version is for low temperature applications (-40°C).
Each port can be configured for MODBUS Master, MODBUS Slave, CCM Slave,
DNP3 Master, DNP3 Slave, or Serial I/O protocol. If any port is configured for
DNP3 Master or Slave, the other ports on the module can only be configured for
DNP3 Master or Slave.
For modules with firmware version 1.32 or later, half-duplex flow control can be
configured using Machine Edition Release 5.90, SP1, SIM 6 or later. Otherwise,
flow control defaults to full-duplex.
Additional module features include:
Port-to-port isolation and port-to-backplane isolation
RS-232, RS-485/422 communication, software-selected
Hardware handshake: RTS/CTS, RFR/CTS for RS-232
Selectable Baud Rates: 1200, 2400, 4800, 9600, 19.2K, 38.4K, 57.6K, 115.2K
Module fault status reporting (Watchdog, Ram Fail, Flash Fail)
Module identity and status reporting, including LED status indicators
Meets CE, UL/CUL 508 and 1604, and ATEX requirements
Flash memory for future upgrades
These modules must be located in an RX3i Universal Backplane.
RX3i Serial Communications can be hot-inserted and removed following the
instructions in the most recent version of the PACSystems RX3i System Manual,
GFK-2314.
For complete installation information, please refer to RX3i and Series 90-30
Installation and Maintenance Requirements document, GFK-2975.
© 2007-2018 General Electric Company. All Rights Reserved.
*Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of
their respective owners.
1
Not compatible with Rackless CPUs, such as CPE400.
IC695CMM002-EJ and IC695CMM002CA-EJ
.
1
PACSystems* RX3i
Serial Communications Modules
Figure 1: CMM004 Front
View

Advertisement

loading

Summary of Contents for GE IC695CMM002CA-EJ

  • Page 1 PACSystems* RX3i Important Product Information IC695CMM002-EJ and IC695CMM002CA-EJ IC695CMM004-EJ, IC695CMM004CA-EJ, and IC695CMM004LT-EJ Serial Communications Modules GFK-2461N April 2018 PACSystems* RX3i Serial Communications modules expand the serial communications capabilities of the RX3i system. Serial Communications module IC695CMM002 provides two independent, isolated serial ports. Serial Communications module IC695CMM004, illustrated at right, provides four independent, isolated serial ports.
  • Page 2: Release Information

    RX3i Serial Communications Modules GFK-2461N Release Information Release 2.02 is a new firmware release implementing a unique system ID for each module to support future RX3i expansion. No change in functionality, performance, or compatibility. Release History Firmware Release Upgrade Kit Comments Version This FW change implements a unique system ID for...
  • Page 3 RX3i Serial Communications Modules GFK-2461N Compatibility Programmer Version Requirements Proficy* Machine Edition Logic Developer 6.00 with SIM 12 or later version is required for DNP3 Unsolicited Response functionality and Analog Input Event Variation configuration. Proficy Machine Edition Logic Developer 5.9 SP1 with SIM 6 is required for half duplex flow control Proficy Machine Edition Logic Developer 5.8 with SIM 2 or newer is required to use SPL Proficy Machine Edition Logic Developer 5.6 with SIM 10 or newer is required to use DNP3 Proficy Machine Edition Logic Developer 5.6 with SIM 6 or newer is required to use the CMM...
  • Page 4 Each port can be configured for DNP3 Master or DNP3 Slave protocol. If any port is configured for DNP3 Master or Slave, the other ports on the module can only be configured for DNP3 Master or Slave. These modules do not support GE Intelligent Platforms special MODBUS commands for use with a Daniels Flow Computer.
  • Page 5 DO I/O. To prevent this, all exchange control bits must be cleared by the application logic on the initial PLC logic scan or upon detection of CMM module removal. Detailed Documentation Refer to the PACSystems RX3i System Manual, GFK-2314, for all further details. It may be downloaded at the following location: https://ge-ip.force.com/communities/en_US/Documentation/PACSystems-RX3i-System-Manual-GFK-2314-en-US.

This manual is also suitable for:

Ic695cmm004-ejIc695cmm002-ejIc695cmm004ca-ejIc695cmm004lt-ej