Plug the VersaPoint and COMBICON connectors into the correct connections.
Perform a function test after replacing the module.
8.3

Validation

Carry out a safety validation every time you make a safety-related modification to the
VersaSafe or PROFIsafe system.
When validating your individual EUC, check the assignment of the sensor and actuator
connections.
Determine whether:
The correct safe actuators are connected to the safety module
The relay contacts are protected
The voltage areas are observed
If the safety-related segment circuit is used, only VersaPoint terminals that are
specifically designed for this safety-related segment circuit are used
The safety module has been parameterized correctly
The variables used in your application program have been linked to the safe actuators
correctly
Please follow the checklist "Validation" on page C-6 during validation.
Chapter 8 Startup and validation
8
8-3