GFK-2734
Plug the VersaPoint and COMBICON connectors into the correct connections.
Perform a function test after replacing the module.
8.3
Validation
Carry out a safety validation every time you make a safety-related modification to the
VersaSafe or PROFIsafe system.
When validating your individual EUC, check the assignment of the sensor and actuator
connections.
Determine whether:
–
The correct safe actuators are connected to the safety module
–
The relay contacts are protected
–
The voltage areas are observed
–
If the safety-related segment circuit is used, only VersaPoint terminals that are
specifically designed for this safety-related segment circuit are used
–
The safety module has been parameterized correctly
–
The variables used in your application program have been linked to the safe actuators
correctly
Please follow the checklist "Validation" on page C-6 during validation.
Chapter 8 Startup and validation
8
8-3