Interchangeability With Earlier Cr192 Modules - GE GEH-5201 Instructions Manual

Synchronous-motor control vith cr192 microprocessor-based starting and protection module
Table of Contents

Advertisement

SECTION 6 - Installation and Start-up
MESSAGE
INVLD
PFTRIP
INVLD
PF DELAY
INVLD STALL
INVLD
RUN TIME
INVLD FLC
INVLD LRC
INVLD
%
SLIP
INVLD
FAR DELAY
INVLD LFREQ
EXPLANATION
MESSAGE
EXPLANATION
INVALID POWER FACTOR TRIP
INVLD
INVALID CURRENT TRANSFORMER
SET-POINT
CT RATIO
SET-POINT
INVALID POWER FACTOR DELAY
INVLD REPLY
INVALID ENTRY FOR THE RESYNC
SET-POINT
SET-POINT
INVALID STALL TIME SET-POINT
INVLD
INVALID FCX DELAY SET-POINT
INVALID RUN TIME SET-POINT
FCX DELAY
INVLD FLDV
INVALID FIELD VOLTAGE SET-POINT
INVALID FULL LOAD CURRENT
INVLD FLD I
INVALID FIELD CURRENT SET-POINT
SET-POINT
INVLD
INVALID FIELD CURRENT
INVALID LOCKED ROTOR CURRENT
FIELD CT
TRANSFORMER SET-POINT
SET-POINT
INVLD
INVALID POWER FACTOR REGULATOR
INVALID PERCENT SLIP SET-POINT
PFREG
SET-POINT
INVALID FAR DELAY TIME SET-POINT
INVLD GAIN
INVALID GAIN SET-POINT
INVLD FLOOR INVALID FLOOR SET-POINT
INVALID LINE FREQUENCY SET-POINT
INVLD
INVALID INCOMPLETE SEQUENCE
INC SEQ
SET-POINT
NOTE: To clear
a trip message such as
PF TRIP or
SCP TRIP,
press
any key on the keypad.
CAUTION:
00 NOT DEFEAT THE MOTOR RESTART
PROTECTION PROVIDED BY THE IlSPM BY
SWITCHING THE CONTROL POWER ON AND OFF,
OR BY DEPRESSING THE SMALL, RECESSED
RESET PUSHBUTTON AT THE TOP REAR OF THE
MODULE CASE. EITHER ONE
OF
THE ABOVE
ACTIONS RESETS THE STALL TIME COUNTERS
WHICH DEFEATS MOTOR PROTECTION FROM
FREQUENT RESTARTS.
6.6 Interchangeability with
earlier CR192 models
Also remove the V130L20 MOV from the resistor
assembly.
The CR192 -C and -D f!SPM modules are physically inter-
changeable with the -A and -8 models. However, if an -A or -
B model is substituted for a -C or -D model, it will be
necessary to install jumpers across the external resistor
assembly as follows:
Install
JUMPER #1
JUMPER #2
JUMPER #3
JUMPER #4
Between resistor
assembly terminals
(R1) and (+)
(F2) and (-)
(V+) and (E+)
(V-)
and (E-)
WARNING:
REMOVE THE ABOVE JUMPERS
AND RECONNECT THE MOV, IF THE CR192
-C
OR -0 MODEL IS RE-INSTALLED IN PLACE OF
THE
-A
OR
-B
VERSION.
We recommend that prominent tags be attached to
each of the above jumpers with wording such as:
WARNING:
REMOVE THIS JUMPER IF THE
CR192
-C
OR -0 IlSPM IS RE-INSTALLED IN
PLACE OF THE -A OR
-B
VERSION.
27

Advertisement

Table of Contents
loading

Table of Contents