Contact data for the safety relay used [...]
Switching power range (guide value)
Contact resistance
Immunity to short-circuiting
Maximum switching capacity (DIN EN 60947-4-1, DIN EN 60947-5-1)
AC 1
AC 15
DC 1
DC 13
Maximum interrupting rating for ohmic load ( = 0 ms)
24 V DC
48 V DC
110 V DC
250 V DC
250 V AC
Maximum interrupting rating for inductive load ( = 40 ms)
24 V DC
48 V DC
110 V DC
250 V DC
Clock outputs
Number
Supply
Maximum switching current
Simultaneity
Derating
Status indicators
Diagnostic indicators
Alarm inputs
Number
Supply
Typical input current
Simultaneity
Derating
Status indicators
Diagnostic indicators
GFK-2734
60 mW to 1500 W (VA)
 100 m (when new)
1000 A SCPD (6 A gG backup fuse)
250 V/6 A
230 V/3 A
24 V/6 A
24 V/5 A/0.1 Hz
144 W
96 W
66 W
63 W
1500 VA
35 W
35 W
35 W
35 W
2
From U
15 mA short-circuit and overload protection, approximately
100%
No
None
None
2
From clock outputs UT1 and UT2
5.5 mA
100%
No
One green LED per alarm input
(see "Local diagnostic and status indicators" on page 2-10)
None
Chapter 11 Technical data and ordering data