GE VersaSafe VersaPoint IC220SDL840 User Manual page 107

Module with safe digital relay outputs
Table of Contents

Advertisement

A Appendix: PROFIsafe terms used in the manual
Consecutive number
CRC
F-CPU
F_Destination_Address
F-Parameter
F-I/O device
F-Slave
F_Source_Address
GFK-2734
Some of the terms that are used in connection with PROFIsafe in this manual are
described below.
A definition of PROFIsafe terms is also provided in the PROFIsafe profile.
Consecutive number
Method for ensuring that the safe data is transmitted completely and in the correct order.
Cyclic Redundancy Check
A cyclic redundancy check is used to verify the validity of the process data contained in the
safety telegram, check whether the assigned address relationships are correct, and verify
the safety-related parameters. This value is part of the safety telegram.
Failsafe control system, safe controller
F-Parameter; PROFIsafe destination address; address of the safe device
(see also "F-Parameter")
(According to PROFIsafe system description, Version 09, November 2007)
F-Parameters contain information for adapting the PROFIsafe layer to specific customer
specifications and for checking the parameterization by means of a separate method
(diverse). The main F-Parameters are:
F_S/D_Address
A unique address for F-Devices within a PROFIsafe island. The
(F-Address for
technology part of the F-Device compares the value with the
short)
address switch locally or with an assigned F-Address in order to
check the authenticity of the connection.
F_WD_Time
Specifies the millisecond value for the watchdog timer. The timer
monitors the time that elapses until the next valid PROFIsafe
message is received.
F_SIL
Indicates the SIL that the user can expect from the relevant
F-Device. It is compared with the manufacturer's specification that
is stored locally.
F_iPar_CRC
A checksum that is calculated from all iParameters of the
technology-specific part of the F-Device.
F_Par_CRC
A CRC signature, which is created via all F-Parameters and
ensures error-free transmission of the F-Parameters.
Failsafe I/O device; safe input and/or output modules
Modules with integrated safety functions, which are approved for safety-related operation.
Failsafe slave
F-Parameter; PROFIsafe source address; address of the safe controller
(see also "F-Parameter")
Chapter A Appendix: PROFIsafe terms used in the manual