Configuration data
PROFIBUS DP
master
SIPROTEC PROFIBUS DP - Bus mapping 6MD662/3/4
C53000-L1840-B011-03
Standard mapping 3-1: 1FH 1FH 1DH DFH 2DH
Standard mapping 3-2: 1FH 1FH 1FH 19H 29H
Standard mapping 3-3: 1FH 1FH 1DH DFH 2DH
Standard mapping 3-4: 1FH 1FH 1DH DFH 2DH
At the configuration of a PROFIBUS DP slave of the SIPROTEC devices in the param-
eterization system of the PROFIBUS DP masters are to select the following modules
for the 6MD662/3/4 standard mappings and to allocate associated addresses in the
I/O addressing range of the PROFIBUS DP master:
Standard mapping 3-1:
Module
0
Input - 16 Bytes
1
Input - 16 Bytes
2
Input - 14 Bytes
3
Input - 16 Words, consistent
4
Output - 14 Bytes
Standard mapping 3-2:
Module
0
Input - 16 Bytes
1
Input - 16 Bytes
2
Input - 16 Bytes
3
Input - 10 Bytes
4
Output - 10 Bytes
Standard mapping 3-3:
Module
0
Input - 16 Bytes
1
Input - 16 Bytes
2
Input - 14 Bytes
3
Input - 16 Words, consistent
4
Output - 14 Bytes
Data of the PROFIBUS DP messages
(78 bytes input-, 14 bytes output direction)
(58 bytes input-, 10 bytes output direction)
(78 bytes input-, 14 bytes output direction)
(78 bytes input-, 14 bytes output direction)
Order number
Order number
Order number
Input address
Output address
Adr_Ix
Adr_Ix + 16
Adr_Ix + 32
Adr_Ix + 46
Adr_Ox
Input address
Output address
Adr_Ix
Adr_Ix + 16
Adr_Ix + 32
Adr_Ix + 48
Adr_Ox
Input address
Output address
Adr_Ix
Adr_Ix + 16
Adr_Ix + 32
Adr_Ix + 46
Adr_Ox