Technical Data - YASKAWA CP 040 RS422/485 Manual

For vipa system slio
Table of Contents

Advertisement

Hardware description

Technical data

3.3 Technical data
Order no.
Type
Module ID
Current consumption/power loss
Current consumption from backplane bus
Current consumption from load voltage L+ (without load)
Power loss
Status information, alarms, diagnostics
Status display
Interrupts
Process alarm
Diagnostic interrupt
Diagnostic functions
Diagnostics information read-out
Supply voltage display
Group error display
Channel error display
Point-to-point communication
PtP communication
Interface isolated
RS232 interface
RS422 interface
RS485 interface
Connector
Transmission speed, min.
Transmission speed, max.
Cable length, max.
Point-to-point protocol
ASCII protocol
STX/ETX protocol
3964(R) protocol
RK512 protocol
USS master protocol
Modbus master protocol
Modbus slave protocol
Special protocols
38
040-1CA00
CP 040 RS422/485
0E41 1700
125 mA
10 mA
1 W
yes
yes, parameterizable
no
yes, parameterizable
yes, parameterizable
possible
green LED
red LED
red LED
ü
ü
-
ü
ü
Terminal module
150 bit/s
115.2 kbit/s
1200 m
ü
ü
ü
-
-
ü
ü
-
HB300 | CP | 040-1CA00 | en | 18-28
VIPA System SLIO

Advertisement

Table of Contents
loading

This manual is also suitable for:

040-1ca00

Table of Contents