Serial communication protocols
3964(R) > Parameter data of 3964(R)
Name
Bytes
OPTION11...14
4
OPTION15
1
OPTION16
1
1) This record set may only be transferred at STOP state.
2) Value depends on the host system.
DIAG_EN: Diagnostic
interrupt
BAUD: Transfer rate
PROTOCOL
70
Function
reserved
Operating mode
Line assignment
Here you activate respectively deactivate the diagnostic function.
Byte
Bit 7 ... 0
0
Range of values:
n
00h: deactivate
40h: activate
n
Default: 00h
Speed of the data transfer in bit/s (baud). There are the following range of values; other
values are not permitted.
Range of values:
Hex
Baud
00
9600
01
150
02
300
03
600
04
1200
05
1800
Default: 00h (9600Baud)
n
Protocol, which is to be used. This setting influences the structure.
Range of values: 03h: 3964
Range of values: 04h: 3964R
Default: 03h
n
Default
DS
00h
80h
00h
80h
00h
80h
Hex
Baud
06
2400
07
4800
08
7200
09
9600
0A
14400
0B
19200
HB300 | CP | 040-1CA00 | en | 18-28
VIPA System SLIO
IX
SX
310Dh ...
0Eh ... 11h
3110h
3111h
12h
3112h
13h
Hex
Baud
0C
38400
0D
57600
0F
76800
0E
115200
10
109700