YASKAWA CP 040 RS422/485 Manual page 71

For vipa system slio
Table of Contents

Advertisement

VIPA System SLIO
OPTION3: Character frame
Data bits
Parity
Stop bits
OPTION4: ZNA
OPTION5: ZVZ
OPTION6: QVZ
HB300 | CP | 040-1CA00 | en | 18-28
Byte
Bit 7 ... 0
0
n
Bit 1, 0: Data bits
00b = 5 Data bits
01b = 6 Data bits
10b = 7 Data bits
11b = 8 Data bits
n
Bit 3, 2: Parity
00b = none
01b = odd
10b = even
11b = even
Bit 5, 4: Stop bits
n
01b = 1
10b = 1.5
11b = 2
n
Bit 7, 6: reserved
n
Default: 13h
(Data bits: 8, Parity: none, Stop bit: 1)
Number of bits onto which a character is mapped.
For the purposes of the parity check, the information bits are expanded by the parity bit.
The value of the parity bit ("0" or "1") completes the value of all the bits to obtain a pre-
arranged state. If the parity was not specified, the parity bit is set to "1" but it is not evalu-
ated.
The stop bits are appended to each character and signify the end of the character.
The delay time that must expire before a command is executed. The ZNA is specified in
units of 20ms.
Range of values: 0 ... 255
Default: 0
n
The character delay time (ZVZ) defines the maximum time that may expire between two
characters of a single telegram during the reception of the telegram. The ZVZ is specified
in units of 20ms.
When the ZVZ=0 the character delay time (ZVZ) will be calculated automatically (about
double character time).
Range of values: 0 ... 255
Default: 10
n
The delayed acknowledgment time defines the maximum time for the acknowledgment
from the partner when the connection is being established. The QVZ is specified in units
of 20ms.
Range of values: 0 ... 255
n
Default: 10
Serial communication protocols
3964(R) > Parameter data of 3964(R)
71

Advertisement

Table of Contents
loading

This manual is also suitable for:

040-1ca00

Table of Contents