4.3.3 Examples

Send data without frag-
mentation
Send data with fragmenta-
tion
HB300 | CP | 040-1CA00 | en | 18-28
If the Telegram-Info-Byte is 04h, an additional offset is entered. Otherwise there is no
Offset in the telegram. Calculating the Offset with fragmented transfer:
Data_Offset = (Fragment_counter + 1) × (IO_Size-1) -7 + Offset
n
Data_Offset:
Offset of the data in the input area
n
Fragment_counter:
Absolute number of fragments
n
IO_Size:
Number of used bytes in the address area
n
Offset:
Offset value in the telegram
Here the received user data of the serial communication may be found.
Bit 3...0
Reserved for sending
Bit 7...4
n
8h: Acknowledgement: Idle state
n
Ah: Acknowledgement: input area free for new data
n
Bh: Command: Execute a reset on the CP
IO-Size = 60byte, length = 40byte
Host system
Byte
Function
0
0Ah Command
1
00h Telegram-Info
2
00h Length high byte
3
28h Length low byte
4...43
User data byte 0...39
44...59
is not used
IO-Size = 16byte, length = 50byte
Header Host system
Byte
Function
0
09h Command
1
00h Telegram-Info
2
00h Length high byte
3
28h Length low byte
Principal communication via back plane bus > Examples
Byte
Function
u
t
0
A0h Acknowledgement
Byte
Function
u
Deployment
CP
CP
49