Hybrid Cabinet Bushing

6.6 Technical data

6.6
Technical data
Table 6- 1
Technical data
DC link voltage
Current-carrying capacity of the DC link
(T
ambient
Current-carrying capacity of the
electronics
Mounting position / type of construction
Cooling method
Installation altitude
Current derating
Dimensions
(W x H x D; without connectors and
caps)
Weight
Degree of protection
The Hybrid Cabinet Bushing fulfills the same thermal and mechanical specifications as the
S120M.
The derating characteristic of the S120M regarding the installation altitude and the
temperature also apply to the Hybrid Cabinet Bushing.
6.6.1

Characteristics

● If the components are operated at increased ambient temperatures (40 to 55 °C) then the
DC link current must be appropriately reduced.
Figure 6-4
114
Technical data of the Hybrid Cabinet Bushing
< 40 °C)
Output current as a function of the ambient temperature
Unit
6SL3555-2DA00-0AA0
V
510 ... 720
DC
A
25
DC
A
10
DC
Any
Natural convection
m
See Chapter "System data" (Page 43)
See Chapter "System data" (Page 43)
mm
139 x 139 x 72
kg
0.85
IP65
SINAMICS S120M Distributed Drive Technology
Manual, (GH12), 12/2014, 6SL3097-4AW00-0BP3