Installing the 24 V terminal adapter

Figure 7-3
The 24 V terminal adapter can be mounted on any Adapter Module 600. The corresponding
cutout must be opened on the protective cover of the DC link using pliers. The 24 V terminal
adapter is snapped on and is retained using the screw provided (tightening torque: 0.5 Nm).
Screw: SHR, PT-TORX K30-3, 0X16-ST-A2F WN1452 / company EJOT
The 24 V terminal adapter is suitable for connecting conductor cross-sections of 0.5 mm
to 6 mm
delivery of the Line Modules and Control Supply Modules (article number 6SL3162-2AA00-
0AA0).
NOTICE
Damage caused by improper mounting of the 24 V terminal adapter
Improper mounting of the 24 V terminal adapter can cause it to be damaged.
• Do not connect or disconnect the 24 V terminal adapter when 24 V is applied.
• Only connect or disconnect the 24 V terminal adapter vertically in relation to the front
Note
Fixing the 24 V terminal adapter
• Once attached, the 24 V terminal adapter must be screwed tight using the screw
supplied.
SINAMICS S120M Distributed Drive Technology
Manual, (GH12), 12/2014, 6SL3097-4AW00-0BP3
Mounted 24 V terminal adapter
. The 24 V terminal adapter and associated screw are included in the scope of
2
panel.
Cabinet design and EMC S120M
7.2 24 V DC supply voltage
up
2
121