Siemens SINAMICS S120M Manual page 44

Distributed drive technology
Hide thumbs Also See for SINAMICS S120M:
Table of Contents

Advertisement

System overview
2.5 System Data
Environmental conditions
Vibratory load
Long-term storage in the transport packaging
Transport in the transport packaging
Operation (central components)
Operation (distributed components)
Shock load
Long-term storage in the transport packaging
Transport in the transport packaging
Operation (central components)
Operation (distributed components)
Climatic environmental conditions
Long-term storage in the transport packaging
Transport in the transport packaging
Operation
Permissible coolant temperature (air) and installation
altitude during operation
Table 2- 13
Certificates
Certificates
Declarations of Conformity
Approvals
44
Class 1M2 in accordance with EN 60721-3-1
Class 2M3 in accordance with EN 60721-3-2
Class 3M1 in accordance with EN 60721-3-3
Class 3M3 in accordance with EN 60721-3-3
Class 1M2 in accordance with EN 60721-3-1
Class 2M3 in accordance with EN 60721-3-2
Class 3M1 in accordance with EN 60721-3-3
Class 3M3 in accordance with EN 60721-3-3
Class 1K4 according to EN 60721-3-1 temperature: -25° C ...
+55° C
Class 2K4 according to EN 60721-3-2 temperature: -40° C ...
+70° C
Class 3K3 according to EN 60721-3-3
Temperature +0 °C ... +40 °C (central SINAMICS S120
components and AM600)
Temperature -15 °C ... +40 °C (distributed SINAMICS
S120M components)
Relative humidity 5% ... 90%
Oil mist, salt mist, ice formation, condensation, dripping water,
spraying water, splashing water and water jets are not permitted
Above 2,000 m installation altitude, refer to the characteristic for
voltage derating
Adapter Modules 600
0 °C ... +40 °C and up to 1,000 m installation altitude without
derating
Other distributed components
-15 °C ... +40 °C and up to 1,000 m installation altitude
without derating
>40 °C ... +55 °C see characteristic for current derating.
Installation altitude >1,000 m up to 4,000 m, see characteristic
for current derating or reduction of the ambient temperature by
3.5 K per 500 m.
Above 2,000 m installation altitude, see characteristic for voltage
derating
CE (Low-Voltage and EMC Directives)
ULus
SINAMICS S120M Distributed Drive Technology
Manual, (GH12), 12/2014, 6SL3097-4AW00-0BP3