INX***DH-F199-IE2-***, INY***DH-F199-IE2-***
Installation
3.2

Mounting Instructions

The inclination sensors are pre-calibrated devices that can be put into immediate operation
following easy installation with a three point mount. The mounting surface must be flat and free
of dust and grease.
Depending on the sensor model, pay attention to the correct orientation of the sensor for
inclination measurement when mounting.
The following figures show the correct axis orientation for each model.
INX***DH-F199-IE2-***
+X
Figure 3.1
INY***DH-F199-IE2-***
X = 0°
-X
Figure 3.2
Fastening with Screws
We recommend hexagon head screws with M6 or UNC 1/4 for the best possible and most
secure mounting. Use all three screws for mounting. Restrict the tightening torque to the range
of 10 Nm ± 10 % for the screws. The M12 connectors are to be perfectly aligned and screwed
to the end with a tightening torque in the range of 0.4 ... 0.6 Nm. Use all three screws for
mounting, and use the same tightening torque for all the screws.
-X
X = 0°
1-axis sensor
+X
2-axis sensor
-Y
Y = 0°
+Y
11