Mounting - Pepperl+Fuchs VIM6 Series Manual

Vibration sensors
Hide thumbs Also See for VIM6 Series:
Table of Contents

Advertisement

VIM6* Vibration Sensors
Installation
3.2

Mounting

Prerequisites
Mounting the vibration sensor on the mounting surface:
The mounting surface must be clean and flat, i.e., free of paint, rust, etc.
The measuring head surface of the vibration sensor must lie flat on the mounting surface.
The vibration sensor is fitted with an M8 screw thread as standard. Insert the screw thread
into a threaded hole in the mounting surface. If the thread in the hole is different, thread
adapters are available as an accessory.
Mounting the Vibration Sensor
For safe and error-free operation, observe the following requirements during mounting:
Mount the vibration sensor on the mounting surface correctly to obtain accurate data.
Avoid mounting the vibration sensor on auxiliary structures. If it is absolutely necessary to
use auxiliary structures, make sure these are designed to be as rigid as possible.
Earth and ground loops are among the most common problems when using measuring
setups with sensitive sensor technology. These loops are caused by unwanted differ-
ences in potential in the circuit between the sensor and the control interface. As a
countermeasure, we recommend our standard grounding concept or, depending on the
application, our alternative grounding concept
Make sure that the ground connection is electrically safe.
1.
Screw the vibration sensor into the threaded hole in the mounting surface using a hexagon
wrench (SW 24) at a tightening torque of 8 Nm.
2.
For plug versions: Connect the connection cable and note that the tightening torque of the
connector's M12 union nut must not exceed 0.4 Nm.
13