INX***DH-F199-IE2-***, INY***DH-F199-IE2-***
Analog Interface Programming
Programming via analog inputs SET 1 and SET 2
1. Connect the operating voltage to pins 1 and 4 of the M12x1, 8-pin connector.
2. Apply a positive voltage (5 V ... 30 V, Rin > 110 KΩ) on the relevant inputs SET 1 and/or SET
2 for at least 100 ms for programming a function.
A timer starts when a positive voltage is recognized. The voltage must be held for at least
100 ms. If the voltage is applied for less time, the timer will be reset.
3. Release the voltage to lock the position.
6.2

Preset Value

Function
Description
Preset Value
The current position
value is set to the mid
angle (2-axix) and
zero position (1-axis).
Table 6.2
6.3

Invert Direction

To use this analog programming option, the inclination sensor must first be set to the
preset/direction mode (teach 0) and the "compl" function has to be set to parameter 2 (compl 2)
via RS-232 interface.
Function
Description
Invert Direction Inverts measurement
direction from
clockwise (standard)
to counterclockwise
(inverted)
Table 6.3
Programming Input
Explanation
Apply 5 V ... 30 V (Rin
With a 2-axis sensor, the preset
> 110 KΩ) on SET 1
function is applied to both axes
simultaneously. There is no
separate preset function for each
axis.
Programming Input
Explanation
Apply 5 V ... 30 V (Rin >
To set the inversion of direction,
110 KΩ) on SET 2 to set
apply a continuous high signal (5
counter-clockwise
V ... 30 V) to SET 2 input. As long
direction (inverted)
as the applied signal on SET 2 is
Apply GND, low-signal
greater than 5 V, the direction of
or no connection to set
measurement is always inverted.
to clockwise direction
(standard)
Default
Default