Setting zone's climatic curve parameters
(accessible only with installer password)
Menu → "Settings" → "Zone Clim. Curve"
− press the ► key so that the number is highlighted on the
right of the word "Zone";
− use the ▲ and ▼ keys to change the zone number;
− press the ● key.
The following is displayed:
Outdoor reset
"
"
90
0
-15
T Outside [°C]
"
The "Comp. T. @ T.ext. Max" parameter, if other than 0, trans-
forms the climatic curve from linear to quadratic allowing you to
best adapt the variation of the setpoint to the variation of the
outdoor temperature.
The resulting quadratic climatic curve will have three parame-
ters:
− Heat. Set. Max
− Baseline Outdoor Temp.
− T. Out. Min
of the basic linear climatic curve and a value of the Heat. Set.
Min. diminished by the value of the parameter "Comp. T. @
T.ext. Max", as can be seen in the example in the figure.
Delivery Temp.
(°C)
Max. Heating Set.
Min. Heating Set.
Baseline Outdoor Temp.
Min Outdoor Temp.
9
When more than one direct zone activates a heat request
at the same time, the delivery setpoint will be equal to the
highest setpoint of the zones making the request.
9
To set the direct zone with a fixed setpoint, the zone setpoint
values "Max. Set. CH" and "Min. Set. CH" must be equal.
Des. Supply T.
82.0
"
"
Bas. Supply T.
40.0
"
"
WW Shutdown
21.0
"
"
Bas. Outd. T.
21.0
35
"
"
Des. Outd. T.
-4.0
"
"
"
Comp. T. @ T.ext. Max
Outdoor Temp. (°C)
Shutdown Temp.

5.6 Programming the zone

By default the schedule timer is disabled.
To start up a request from the zone, just close the zone request
contact. In that event the thermal unit (or the cascade of ther-
mal units) will start up with a setpoint equal to the value cal-
culated on the zone climatic curve increased by the "Zone Ex-
tra Setpoint" value and, if it is a mixed zone, the mix valve will
modulate to maintain the delivery temperature of the zone at
the setpoint calculated.
If there is no external sensor, the delivery setpoint of the ther-
mal unit will be equal to the maximum setpoint of the climatic
curve.
°C
"
"
To activate zone programming:
°C
Menu → "Settings" → "Clock Settings"
"
"
°C
"
"
°C
"
"
Settings
°C
"
"
"
"
Clock Settings
"
Appliance Configuration
"
External Zone Settings
"
Ext. Zone Climatic Curve
"
Confirming with ● the following screen is displayed:
Clock Settings
"
CH Clock
"
"
DHW Clock
"
CH Ext. Zones Clock
"
− with the ▲ / ▼ keys select "CH Zones clock"
− with the ► key move to "Disabled", change it to "Ena-
bled" with the ▲ / ▼ keys
− confirm with the ● key
Go to:
Menu → "Clock program"
Confirming with the ● key:
Clock Program
"
Program CH Zone Ext.
"
Program Group
"
Holiday Settings
"
Season Settings
"
At this point select the number of the zone to be programmed
and confirm with the ● key.
External Zone
"
Program Comfort Period
"
Comfort Setpoint
"
ECO Setpoint
"
Out of interval setpoint
"
128
p
"
"
"
"
"
Disabled
"
Disabled
"
"
Disabled
"
"
"
1
"
1
"
"
"
2
"
1
"
20.0
"
5.0
°C
"
"
Anti Fr
"
"
"
"
"
°C
"
"
"
"