Error
Diagnostic
Device
code
code
46
06
BU
46
07
BU
47
-
BU
48
-
BU
50
#
BU
50
00..07
BU
51
#
BU
51
00..07
BU
52
#
BU
52
01
BU
52
02
BU
52
03
BU
53
01
BU
58
-
BU
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
15 Addendum 1: List of fault status messages of LMV51... system
Display
Programstop active
Program stop "STOP_DR_POSTP" in
Phase 72 active
Programstop active
Program stop "STOP_PREP2" in Phase
76 active
No Start Release for Gas
Start release gas = off
2 Flame Signals with 1 Detector
System parameterized for 1-detector
Operation
operation but 2 flame signals present
Internal Fault Basic Unit
Fault during key value check
Internal Fault Basic Unit
Number of time block in which the fault
was detected
Internal Fault Basic Unit
Time block overflow
Internal Fault Basic Unit
Number of time block in which the fault
was detected
Internal Fault Basic Unit
Stack error
Internal Fault Basic Unit
Stack overflow
Internal Fault Basic Unit
Value dropped below preset minimum limit
Internal Fault Basic Unit
Test values in stack range exceeded
Internal Fault Basic Unit
Faulty reset state has occurred
Parameter Set damaged
Internal communication (uC1 <> uC2)
Meaning for the LMV5x system
Troubleshooting
*1)
*1)
*1)
*1)
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL...
parameters.
Otherwise, replace defective basic unit
205/278
CC1P7550en
01.10.2003