Siemens LMV5 Series Basic Documentation page 143

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Parameterdarstellung auf Basis der Menüstruktur AZL - Ebene «OEM» - Auslieferstand Siemens Landis&Staefa
Menu level 1
Menu level 2
Menu level 3
Displayed
Values
ProductID
SW Version
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
7 Display and operating unit AZL5...
Menu level 4
Menu level 5
Menu level 6
O2 Sensor
SupAirTempSen
s
FlueGasTempSe
ns
MaxTempFlGas
Gas
MaxTempFlGas
Oil
Current O2
Value
SupplyAirTemp
FlueGasTemp
QGO
SensorTemp
QGO
HeatingLoad
QGO Resistance
ASN
ProductionDate
SerialNumber
ParamSet Code
ParamSet Vers
Description
Configuration of oxygen sensor
Configuration of supply air temperature input
Configuration of flue gas temperature input
Switch-off limit of flue gas temperature
Switch-off limit of flue gas temperature
Current O2 value
Supply air temperature in °C
Flue gas temperature in °C
Sensor temperature of QGO in °C
Control value of QGO heating in 0.1%
Internal resistance of QGO's Nernst cell
Type reference
Date of production
Serial number
Preselected parameter set: customer code
Preselected parameter set: version
SW version of O2M
Value range
Access
Default
LMV51 LMV52
rights
parameter
setting
no sensor
Service
no sensor
QGO20
no sensor
Service
no sensor
Pt1000
Ni1000
no sensor
Service
no sensor
Pt1000
Ni1000
0..400°C
Service
400°C
0..400°C
Service
400°C
User
0..100%
User
-
-100..923 °C
User
-
-100..923 °C
User
-
-100..923 °C
User
-
0..100%
User
-
0..1000 Ohm
User
-
User
1..15 characters
User
"PLL52.110
A200"
01.01.00..31.12.99
User
-
01-01-00..12-31-99
0..65535
User
-
0..255
User
20
0..65535
User
400
0..65535
User
-
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
143/278
CC1P7550en
01.10.2003

Hide quick links:

Advertisement