Loss-of-flame test

SLT test

AZL5... menu structure
with parameter definitions
Siemens Building Technologies
HVAC Products

7.4 Safety check function

The safety check function may only be performed by authorized staff.
It is possible to activate
• the floss-of-flame test, and
• the SLT test
The loss-of-flame test is triggered manually with the AZL5... and produces an
interruption of the flame signal.
Using safety shutdown «Loss of flame», the LMV5... must shut the burner down.
Activation of the SLT test negates the internal controller and temperature limiter
function.
The setpoint and the temperature limiter switch-off threshold will be ignored.
The burner will be switched on and the output automatically increased to 100 %.
After safety shutdown by STL lockout or manual selection, the SLT test can be
deactivated again.

7.5 Menu and parameter lists

For each line, a parameter for the AZL5... menu is defined.
Name of column
Menu level
Description
Value range
Access rights
Basic parameter setting
LMV51...
LMV52...
The parameter list shown on the next pages represents the preselection for the following
type of system:
LMV52.200A2
SQM45...
The basic parameter settings made in the factory can vary, depending on
customer- or country-specific requirements.
The preselected values listed are valid for the following parameter set:
Parameter set code: 20
Parameter set version: 400
If required, the code or version of the parameter set can be displayed on the AZL5...
In that case, select menu item «Factory ID» from the menu of the relevant device.
Basic Documentation LMV51...
7 Display and operating unit AZL5...
Description
This parameter name or this submenu level corresponds to
the name on the menu
Brief explanation of the parameter or of the submenu level
Definition of setting limits within which the parameter can be
changed
Definition of access rights. Parameters can be set by:
User :
Plant operator
Service : Heating engineer
OEM :
Boiler / burner manufacturer
Factory-set parameter
Line marked with an "x": Line will be displayed with the
LMV51... system
Line marked with an "x": Line will be displayed with the
LMV52... system
119/278