Siemens LMV5 Series Basic Documentation page 225

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Error
Diagnostic
Device
code
code
A9
09
FuM
A9
0A
FuM
A9
0C
FuM
A9
0D
FuM
A9
0E
FuM
A9
15
FuM
A9
16
FuM
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
15 Addendum 1: List of fault status messages of LMV51... system
Display
Internal Fault VSD Module
Fault during stack test
Internal Fault VSD Module
Max IRQ speed reached
Alarm from VSD
VSD reports a fault to the VSD module
Control Range Limitation VSD
VSD module could not offset speed
Module
differential within its control limits
Internal Fault VSD Module
Fault during the speed calculation test
Internal Fault VSD Module
CAN bus fault, disturbed CAN bus
transmissions
Internal Fault VSD Module
CRC fault of a parameter page
Meaning for the LMV5x system
Troubleshooting
*1)
Possibly interference on the line to the speed sensor, check
cable routing, use shielding
*1)
Fault has been triggered by the VSD.
Read VSDs error code.
Check VSD settings (ramps, motor settings), increase ramp
time on VSD and basic unit, if necessary.
Check combination VSD / motor size
Check to see if the current interfaces of VSD and VSD
module use the same setting (0/4...20 mA).
Standardize the speed.
!! Note !!
After standardizing the speed -> check setting of
combustion mixture !
*1)
If fault occurs sporadically: Check CAN bus wiring.
Improve EMC.
Check terminating resistors and correct, if necessary
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL...
parameters.
Otherwise, replace defective basic unit
225/278
CC1P7550en
01.10.2003