Shutting Down And Powering Off The Ups - Huawei UPS5000-H-1200 Series User Manual

Table of Contents

Advertisement

UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)

5.2 Shutting Down and Powering Off the UPS

Context
If the bypass is normal, the UPS transfers to bypass mode after the inverter is shut down; if
the bypass is abnormal, the UPS supplies no power after the inverter is shut down. Before
shutting down the UPS, ensure that all loads have been shut down.
Procedure
Step 1 Shut down the inverter.
If the inverter shuts down and the bypass is normal, the UPS transfers to bypass mode. The
Bypass mode alarm is displayed on the LCD.
Figure 5-5 Normal bypass
Issue 01 (2020-07-15)
Shutting down the inverter on the LCD
Choose Common Functions > Inv. OFF. After confirmation, the inverter is shut down.
You can also choose System Info > Maintenance > Inv. OFF to shut down the inverter.
Shutting down the inverter on the WebUI
Choose Monitoring > UPS System > Running Control, and click Inv. OFF.
Copyright © Huawei Technologies Co., Ltd.