Query - Huawei UPS5000-H-1200 Series User Manual

Table of Contents

Advertisement

UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
Item
Class 2 grid hiber. time
(d)
Thres. of low batt. SOC
over dry contact(%)
Thres. of low batt. volt.
over dry contact(V/cell)
Battery String Summary
Item
No. of iBOX
iBAT start No.
iBAT end No.

4.2.4 Query

On the Query page, you can query Historical Alarm, Battery Test Records, and
Performance Data, and perform Export Data.
Figure 4-47 Query
Item
Historical
Alarm
Battery Test
Issue 01 (2020-07-15)
Description
Specifies the hibernation time for class 2 power
grids.
If an output dry contact is set to Low battery
SOC and the battery SOC is lower than this
threshold, the output dry contact generates a
signal.
Lead-acid battery: If Batt. Volt. Below Threshold
is set for an output dry contact and the battery
voltage is lower than this threshold, the output dry
contact generates a signal.
Lithium battery: If Batt. Volt. Below Threshold
is set for an output dry contact and the minimum
electrochemical cell voltage is lower than the
threshold, the output dry contact generates a
signal.
Description
Number of an iBOX connected to the UPS
Start number of an iBAT connected to the iBOX
End number of an iBAT connected to the iBOX
Description
Queries historical alarms of the system or components.
Query and export Cap. test logs and Common test logs.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default
Value Range
Value
6
0–15
75
5–80
1.70
1.70–2.10
2.80
2.60–3.20
129