Huawei UPS5000-H-1200 Series User Manual page 179

Table of Contents

Advertisement

UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
Alarm ID
Alarm Name
(Alarm
ID-Cause
ID)
0564-1
Overload
timeout
0565-1
Load impact
transfer-to-byp
ass
0566-1
Output
overload
0570-4
BPM module
abnormal
Issue 01 (2020-07-15)
Severity
Possible Cause
Critical
The loads are
excessive.
Derating
reduces the
rated system
power.
The module
is damaged.
The output is
incorrectly
grounded.
The peak
load current
is excessively
high.
Minor
A
large-power
RCD load is
instantly
connected, or
the output
load
short-circuits.
The inverter
bridge
short-circuits.
Minor
The loads are
excessive.
Derating
reduces the
rated system
power.
The module
is damaged.
Critical
The bypass
fan is
abnormal, or
the
ventilation
channel is
blocked.
The ambient
temperature
exceeds the
Copyright © Huawei Technologies Co., Ltd.
Suggestion
later.
1. Check that there is no overload.
2. Check that the module power is not
derated due to a fan fault.
3. Check that the power grid has no large
asymmetric load.
4. Check that the output is grounded.
5. Check that the peak load rate does not
exceed the specifications.
6. If the alarm persists, replace the power
module.
1. Check the loads.
2. If the loads are normal, replace the
power module.
1. Check that there is no overload.
2. Check that the module power is not
derated due to a fan fault.
3. If the alarm persists, replace the power
module.
1. Check the bypass fans and ventilation
channel. If the fans are faulty, replace
them.
2. Check that the ambient temperature does
not exceed 40° C.
3. Check that there is no overload.
B Alarm List
171