UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
Figure 3-4 Copper bar specifications (unit: mm)
Table 3-2 Recommended cross-sectional areas for power cables
Item
Mains input
Mains input current
Bypass input
Bypass input current
Output
Output current
Battery input
Nominal battery discharge current
(lead-acid
Maximum battery discharge current
battery)
Recommended cable
cross-sectional area
Battery input
Nominal battery discharge current
(SmartLi)
Maximum battery discharge current
Recommended cable cross-sectional area
Equipotential
Recommended cable cross-sectional area
ground point
Issue 01 (2020-07-15)
The rated voltage of the SmartLi is 512 V. The voltage is 408 V at the maximum discharge current.
The currents listed in the table are measured at a rated voltage of 380 V.
When selecting, connecting, and routing power cables, follow local safety regulations
and rules.
Copyright © Huawei Technologies Co., Ltd.
Specifications
2229 A
1823 A
1823 A
2632A
3185A
+
6 x (2 x 240 mm
-
PE
240 mm
2467 A
3096 A
For details, see the IEC-60364-5-52
specifications and SmartLi User Manual.
16 mm
2
)
2
2