UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
Silk Screen
Table 2-5 Indicator description
Indicator
NORMAL
ALM
FAULT
Functions
Issue 01 (2020-07-15)
Description
frequencies and phases between UPS systems, ensuring that two
buses can switch with each other.
BSC cables are hot-swappable.
No parallel cable is required for a single UPS.
Color
Status
Green
Steady on
Blinking at
0.5 Hz
Off
Blinking at 4
Hz
Yellow
Steady on
Off
Red
Steady on
Off
As a control interface for the entire system, the ECM communicates with each module
and provides a bus for communication between the dry contact card and the system
control card. The ECM ensures equalized output currents between modules so that load
power is equally shared.
The ECM provides module working status information to the monitoring system.
The ECM controls the running of a single UPS and a parallel system, and reports the
UPS status information to other monitoring modules.
The system provides three types of CAN communication: monitoring CAN
communication, intra-rack parallel CAN communication, and inter-rack parallel CAN
communication.
Copyright © Huawei Technologies Co., Ltd.
Description
This ECM is the active ECM.
This ECM is the standby ECM and it is ready.
This ECM is not ready or the software of this
ECM is being upgraded.
The ECM software is being upgraded or not
configured.
The ECM has a minor alarm, but it does not need
to be replaced.
The ECM has no minor alarm or the software of
the ECM is being upgraded.
The ECM has a critical alarm.
The ECM has no critical alarm or the software of
the ECM is being upgraded.