Mitsubishi MELSEC-Q Series User Manual page 46

Channel isolated thermocouple input module, gx-configurator-ti sw1d5c-qtiu-e, programmable controller
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
(9) Operating condition setting request (Y9)
(10)User range write request (YA)
(11)Channel change request (YB)
3
- 23
3.3 I/O Signals Transferred to/from Programmable Controller CPU
3.3.2 I/O signal details
(a) This signal is turned ON when enabling the following setting contents.
• Conversion enable/disable setting (Un\G0)
• CH
Time/Count/Moving average/Time constant setting (Un\G1 to Un\G8)
• Averaging processing selection (Un\G24,Un\G25)
• Warning output enable/disable setting (Un\G46)
• Scaling valid/invalid setting (Un\G58)
• CH
Scaling range upper/lower limit value (Un\G62 to Un\G77)
• CH
Scaling width upper/lower limit value (Un\G78 to Un\G93)
• CH
Process alarm upper/lower limit value (Un\G94 to Un\G125)
• CH
Rate alarm warning detection period (Un\G126 to Un\G133)
• CH
Rate alarm upper/lower limit value (Un\G134 to Un\G149)
• Disconnection state conversion setting (Un\G164, Un\G165)
• CH
Conversion setting for disconnection state value (Un\G166 to
Un\G173)
(b) When this signal turns ON, the disconnection state monitor signal (XC) and the
warning output signal (XD) turn OFF.
(c) For the ON/OFF timing, refer to the field of the operating condition setting
completion flag (X9).
(a) In offset/gain setting mode
1) This signal turns ON when registering the adjusted value of offset/gain setting
to the flash memory.
2) For the ON/OFF timing, refer to the field of the offset/gain setting mode status
flag (XA).
For offset/gain settings, refer to Section 4.6.
(b) In normal mode
1) This signal turns ON when the user range is restored.
2) For the ON/OFF timing, refer to the field of the offset/gain setting mode status
flag (XA).
For user range restoration, refer to CHAPTER 7.
(a) This signal turns ON when changing the channel for executing the offset/gain
setting.
(b) For the ON/OFF timing, refer to the field of the channel change completion flag
(XB).