7
ONLINE MODULE CHANGE
POINT
(3) Mounting of new module
7.3.5 When user range setting is used and initial setting was made with sequence program (other system
(c) After confirming that the "RUN" LED of the module has turned off, remove the
connector and dismount the module.
Always dismount the module. If you execute mounting confirmation without
dismounting the module, the module will not start properly and the "RUN" LED will
not be lit.
(a) Mount the dismounted module and new module to the other system.
(b) Using the G(P).OGLOAD instruction, save the user range setting values to the
CPU device. Refer to Appendix 4.3 for the G(P).OGLOAD instruction.
(c) Using the G(P).OGSTOR instruction, restore the user range setting set values to
the module. Refer to Appendix 4.4 for the G(P).OGSTOR instruction.
(d) Dismount a new module from the other system, mount it to the slot from where the
old module was dismounted in the original system, and install the connector.
(e) After mounting the module, click the
"RUN" LED is lit. Module Ready (X0) remains OFF.
button and make sure that the
7.3 Online Module Change Procedure
1
2
3
4
5
6
7
8
7
- 24