Error Code (Un\G19); Setting Range (Thermocouple Type) (Un\G20, Un\G21); Setting Range (Offset/Gain Setting) (Un\G22) - Mitsubishi MELSEC-Q Series User Manual

Channel isolated thermocouple input module, gx-configurator-ti sw1d5c-qtiu-e, programmable controller
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
3.4.6

Error code (Un\G19)

(1) Error code that is detected by the Q68TD-G-H01 is stored.
(2) For details of error codes, refer to Section 8.1.
3.4.7

Setting range (thermocouple type) (Un\G20, Un\G21)

(1) This area is for checking the thermocouple type of the Q68TD-G-H01,
which is set in the intelligent function module switch settings 1 and 2.
The setting value of thermocouple type is stored into the area indicated
below for each channel.
Un\G20
(Setting range CH1 to CH4)
Un\G21
(Setting range CH5 to CH8)
(2) Setting value for each thermocouple type is shown below.
3.4.8

Setting range (offset/gain setting) (Un\G22)

(1) This area is for checking the offset/gain setting of the Q68TD-G-H01
which is set in the intelligent function module switch setting 3.
"0" is stored for factory default and "1" is stored for user range setting.
b15 b14 b13 b12 b11 b10
b15
to
b12 b11
CH4
CH8
Table 3.10 Thermocouple type and setting value
Thermocouple type
Thermocouple K
Thermocouple E
Thermocouple J
Thermocouple T
Thermocouple B
Thermocouple R
Thermocouple S
Thermocouple N
0
0
0
0
0
0
Data for b8 to b15 are fixed to "0".
to
b8 b7
CH3
CH2
CH7
CH6
Setting value
0
H
1
H
2
H
3
H
4
H
5
H
6
H
7
H
b9
b8
b7
b6
b5
b4
0
0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH1
3.4 Buffer Memory
3.4.6 Error code (Un\G19)
to
to
b4 b3
CH1
CH5
b3
b2
b1
b0
0: Factory default setting
1: User range setting
3
- 34
1
2
3
b0
4
5
6
7
8