ONLINE MODULE CHANGE
7.3.3
(1) Conversion disable
(2) Dismounting of module
7
7.3 Online Module Change Procedure
- 13
7.3.3 When user range setting is used and initial setting was made with GX Configurator-TI (other system
When user range setting is used and initial setting was made with
GX Configurator-TI (other system is available)
(a) Set conversion enable/disable setting (Un\G0) for all channel conversion disable
and turn Operating Condition Setting Request (Y9) from OFF to ON to stop
conversion.
After confirming that conversion has stopped with the Conversion Completion
Flag (Un\G10), turn off Operating Condition Setting Request (Y9).
(a) After choosing [Diagnosis] - [Online module change] on GX Developer to enter the
"Online module change" mode, double-click the module to be changed online to
display the "Online module change" screen.