Relay Module - Dräger Polytron 7000 Instructions For Use Manual

Type p3u and type p3fb
Hide thumbs Also See for Polytron 7000:
Table of Contents

Advertisement

1) To determine the overall power consumption of the gas detector in the case of use of the relay
or pump module, add up the individual power consumption values.
Ambient conditions during
operation
1) The readability of the display is impaired at temperatures below -20 °C (-5 °F) At negative tem-
peratures, the operability of the gas detector is affected be the increasing sluggishness of the
display.
Ambient conditions during
storage
14.1

Relay module

Power supply
Relay switch outputs
Ambient conditions
Cable entry
Cable core cross-section
Weight
Life span of the buffer battery
for data storage
Temperature
Pressure
Humidity
Temperature
Pressure
Humidity
Operational voltage (DC)
Power consumption
logical channels
principle
contacts
contact rating
temperature resistance of the
cables used
Overvoltage category
Temperature (during opera-
tion)
Temperature (during storage)
Pressure
Humidity
Dräger Polytron 7000
M20 x 1.5; cable diameter 6 mm (0.24") ...
12 mm (0.47")
2
0.5 mm
(AWG 20) ... 2.5 mm
approx. 0.9 kg (2.0 lb), without pump and relay
module
4 years from delivery
–40 ... 65 °C (–40 ... 160 °F)
700 ... 1300 hPa
0 ... 100 % rh, non-condensing
–40 ... 70 °C (–40 ... 150 °F)
700 ... 1300 hPa
0 ... 100 % rh, non-condensing
12 V to 30 V at the gas detector
<2 W
A1, A2, fault
normally energised (for fail-safe operation)
1-pole changeover (SPDT)
5 A at 30 V DC; 5 A at 250 V AC
at least 20 °C above the ambient temperature
occurring during operation.
II
-40 ... 65 °C (-40 ... 160 °F)
-40 ... 70 °C (-40 ... 150 °F)
700 ... 1300 hPa
0 ... 100 % rh, non-condensing
Technical data
2
(AWG 13)
1)