Simatrix Configuration Tips - Siemens DMS8000 MP4.30 Connectivity Manual

Simatrix, telscan, sistore burle/philips ltc8000 light-integration device (external viewer)
Hide thumbs Also See for DMS8000 MP4.30:
Table of Contents

Advertisement

Configuring CCTV network
2.7.3

SIMATRIX configuration tips

Building Technologies
Fire Safety & Security Products
Connecting the monitors (Video network model only)
1. Select and expand the SIMATRIX node.
2. Select and expand the SIMATRIX Video Out folder.
3. Select and expand the Video Monitor folder.
4. Select the video-out node of the SIMATRIX.
5. Drag and drop the Video Out signal to the monitor Video In node (Fig 16).
Fig 16
Connecting SIMATRIX to monitors
Linking the SIMATRIX to the Communication network
Link the SIMATRIX node to the CDI-Net or NK8000.
1. Expand the network folders until you reach the node that represents the net-
work that is physically connected to the SIMATRIX (CDI-Net or NK8000).
2. Select the SIMATRIX node.
3. Drag and drop the SIMATRIX node to the network port node (see Fig 17).
Fig 17
Linking SIMATRIX to NK8223
Use only one of the alarm modes (manual, automatic or stack alarm).
SIMATRIX is not connected over the LAN. It connects via the serial line, typi-
cally to an NK822x unit.
Normally, no special SIMATRIX EPROM needs to be ordered for new units. In
case of installed matrices, check with CCTV support the required upgrading
steps.
In the SIMATRIX tool, you need to set the host protocol to CDDL/CDSF. The
COM physical port settings should then be set to the following values:
048_DMS_DMS8000_Connectivity_Video_MP4.30_A6V10062457_a_en.doc
23
06.2010