Configuration Procedure - Siemens DMS8000 MP4.30 Connectivity Manual

Simatrix, telscan, sistore burle/philips ltc8000 light-integration device (external viewer)
Hide thumbs Also See for DMS8000 MP4.30:
Table of Contents

Advertisement

2.8.2

Configuration procedure

26
Building Technologies
Fire Safety & Security Products
The following are the configuration procedures for a SISTORE unit:
Adding the Video Network Manager
1. Open the Composer project.
2. If not already done, add the Video Network Manager ( 2.2 at p.5)
and the SISTORE driver:
 see 2.2.1 at p.7.
Adding the folder for the SISTORE system
Optionally, create a folder for the SISTORE unit.
Adding the SISTORE node
1. Select the new folder.
2. In the left-hand bar, select the Video folder icon
3. In the menu that appears, select one of the SISTORE icons
– SISTORE AX DVR
– SISTORE MX/MX DVR applying SDK 1.4 (MX firmware V2.5 to V2.81)
– SISTORE CX and SX DVR
– SISTORE MX/MX DVR applying SDK 2.5 (MX firmware V2.81-01 and
higher, with preset position support)
 see Fig 4 at p.8.
Configuring the SISTORE settings
1. Select new SISTORE node and click the Node tab.
Note: By default, the node will be named 'SISTORE xx #nn'. In the Node tab,
you can customise the Description text.
2 Fill in the following fields (see Fig 18and Fig 19):
– Type, to be selected in the drop down list according to the actual number of
video connections.
– IP address of the SISTORE unit, which should match the value as set in the
SISTORE device. You can found the address in the following ways:
For AX, run the SISTORE AX RAS software and start the 'Local Setup'
(the button next to the "SISTORE AX Admin" title of the main window),
then click the Remote Site tab and select the AX unit in the list (the AX
unit has to be first created; here we assume that it has been already con-
figured in the RAS program).
For MX / MX Pro / MX NVS, start the SISTORE MX program, and, in the
program menu, select 'Administration  Configuration  Network'.
For SX / CX, start the 'SISTORE SX/CX Config' program, select the SIS-
TORE unit in the list and just read the IP address in the data window on
the right.
– TCP port (do not change this value unless the default values are also
changed in the CCTV system).
– Username (usually "IVM_SERVER") and password for the configuration of
SISTORE (do not change this value unless you really know what you are do-
ing).