WAGO -I/O-SYSTEM 750-508 Manual page 16

2do 24v dc 2.0a, diagnostics, 2-channel digital output module dc 24 v, shortcircuit protected; high-side switching, with diagnostics
Table of Contents

Advertisement

16
Device Description
Do not exceed maximum current via power contacts!
The maximum current to flow through the power contacts is 10 A.
Greater currents can damage the power contacts.
When configuring the system, ensure that this current is not exceeded. If
exceeded, an additional potential feed module must be used.
Po s: 21.15 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Beschreibung/Funktion/Funktion 750-05xx Fehlerbit @ 5\mo
d_1246860556806_21.doc @ 36596 @ @ 1
In the event of an overload, short circuit or line break, an error bit per channel (bit
0 for channel DO 1 and bit 1 for channel DO 2) is set in the input process image.
Using this bit, the master control can identify the error. After rectifying the error,
the error bit is reset in the input image and the error LED goes off.
Po s: 21.16 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Beschreibung/Funktion/Funktion 750-0508 Kurzschluss @ 5\mod_1246948456748_21.doc @ 36710 @ @ 1
At short-circuit to ground or overload and when the output is set, the output will
change to 0 and will return to 1 after the fault has been cleared.
Po s: 21.17 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Beschreibung/Versorgung/Galvanische Trennung Feld/System @ 3\mod_1233756478750_21.doc @ 27102 @ @ 1
The field level and the system level are electrically isolated from one another.
Po s: 21.18 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Beschreibung/Einsatzbereich/Hinweise/Warnung: Einsatz Variante /xxx-8xx in sicherheitsgerichteten Anwendungen @ 5\mod_1246882860453_21.doc @ 36680 @ @ 1
Using in safety related applications!
When using the I/O module ( 750-508 ) in safety-related applications, the
instructions and connection examples in Section "Use in safety-related
applications" are to be observed!
Po s: 21.19 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Beschreibung/Versorgung/Anordnung bei Einsatz in sicherheitsgerichteten Anwendungen blockweise @ 5\mod_1246876694406_21.doc @ 36674 @ @ 1
Any configuration of the output modules is possible when designing the fieldbus
node. Grouping of module types is not necessary.
Po s: 21.20 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Beschreibung/Einsatzbereich/Einsatzbereich 750-xxxx alle Koppler/Controller ohne Einschränkung @ 3\mod_1232541691906_21.doc @ 26522 @ @ 1
The I/O module 750-508 can be used with all fieldbus couplers/controllers of the
WAGO-I/O-SYSTEM 750.
Po s: 22 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1
WAGO-I/O-SYSTEM 750
750-508 2DO 24V DC 2.0A, diagnostics
Manual
Version 1.2.0

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

750-626750-626/020-000

Table of Contents