Item
IP rating
7.3 Mains Input Electrical Specifications
Table 7-3 Mains input electrical specifications
Item
Rated input
voltage
Input voltage
range
Rated input
frequency
Input frequency
range
Input power
factor (100%
resistive load)
Input harmonic
current (100%
resistive load)
Voltage detection
precision
Generator input
capacity
Inrush current
Static withstand
voltage
7.4 Bypass Input Electrical Specifications
Table 7-4 Bypass input electrical specifications
Item
Bypass input
voltage
Issue 01 (2020-08-06)
Specifications
IP20
Specifications
220 V AC/230 V AC/240 V AC
110–280 V AC; < 176 V AC: derated; 110 V AC: 50% load
50 Hz/60 Hz
50 Hz/60 Hz±4 Hz
0.99(100% load)
≤ 5% (100% load)
2%
≥ 1.5 times the UPS capacity
≤ five times the rated current
320 V AC input, no damage to the UPS (at least 2 hours)
Specifications
220 V AC/230 V AC/240 V AC
Copyright © Huawei Technologies Co., Ltd.
7 Technical Specifications
89