Cold-Starting The Ups Using Batteries - Huawei UPS2000-G-6KRTLL User Manual

Hide thumbs Also See for UPS2000-G-6KRTLL:
Table of Contents

Advertisement

UPS2000-G-6KRTLL
User Manual
Step 2 Set the battery capacity.
Battery Capacity
Step 3 Press and hold ON/MUTE for more than 5s. Release the button when you hear a
beep sound. The UPS starts to work in normal mode.
Figure 5-4 Normal mode
Step 4 After you ensure that the UPS runs properly, switch on the AC output circuit
breaker Q for the UPS to start the load.
----End

5.2.1.2 Cold-Starting the UPS Using Batteries

Step 1 Switch on the external battery circuit breaker (if any).
Step 2 Press ON/MUTE to start the UPS. The UPS will enter the standby mode. Press and
hold SELECT for 1s on a non-setting screen to access the login screen for
parameter settings. The initial password is 123. Enter the correct password to
access the UPS setting mode.
Issue 01 (2020-08-06)
Figure 5-3 Bypass mode
Copyright © Huawei Technologies Co., Ltd.
Description
● Default value: 4 (200 Ah)
● Value range: 1 (50 Ah) to 48 (2400
Ah). The value increases by 50 Ah
each time you press SELECT.
5 Operations
78