Huawei UPS2000-G-6KRTLL User Manual page 64

Hide thumbs Also See for UPS2000-G-6KRTLL:
Table of Contents

Advertisement

UPS2000-G-6KRTLL
User Manual
Alarm
Alarm
ID
Name
03
High
battery
voltage
04
Low
battery
voltage
Issue 01 (2020-08-06)
Severity
Clearance
Condition
Critical
The alarm
is
automatic
ally
cleared
when the
battery
voltage is
lower
than 58 V.
Minor
The
battery
voltage is
higher
than 42 V
and the
mains is
connected
properly.
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on the
Condition
System
The battery
The system
voltage is
shuts down the
greater than
inverter and
60 V for 3s.
transfers to
bypass mode.
The battery
The system
voltage is
cannot supply
lower than
power in
42 V.
battery mode.
If this alarm is
generated in
battery mode,
the power
output will be
disconnected.
4 Control Panel
Suggestion
● Possible cause:
The battery is
faulty.
Measure: Replace
the battery or
discharge the
battery to a normal
voltage.
● Possible cause:
The sampling is
faulty due to
environmental
factors.
Measure: Send the
device to the
maintenance
center.
● Possible cause:
The battery is
faulty.
Measure: Replace
the battery or
charge the battery
to a normal
voltage.
● Possible cause:
The sampling is
faulty due to
environmental
factors.
Measure: Send the
device to the
maintenance
center.
58