Huawei UPS2000-G-6KRTLL User Manual page 78

Hide thumbs Also See for UPS2000-G-6KRTLL:
Table of Contents

Advertisement

UPS2000-G-6KRTLL
User Manual
Alarm
Alarm
ID
Name
55
Excessive
DC
compone
nt
57
Current
sensor
fault
58
Low
output
voltage
Issue 01 (2020-08-06)
Severity
Clearance
Condition
Critical
The alarm
can be
automatic
ally
cleared
for three
times.
After that,
you need
to
manually
clear the
fault or
power off
and
restart
the
device.
Critical
You need
to
manually
rectify the
fault or
power off
and
restart
the
device.
Critical
You need
to
manually
rectify the
fault or
power off
and
restart
the
device.
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on the
Condition
System
The DC
The system
component
shuts down the
of the output
inverter and
voltage is
transfers to
greater than
bypass mode.
200 mV for
20s.
In power-on
The system
mode, the
cannot start
current
the inverter
sampling
and directly
deviation
delivers output
exceeds 10%
in bypass
of the total
mode.
sampling
range.
The output
The system
voltage is
shuts down the
lower than
inverter and
the rated
transfers to
voltage by
bypass mode.
50 V for 3s.
4 Control Panel
Suggestion
● Possible cause:
The half-wave
load power is
too high.
Measure: Locate
the load and
remove it.
● Possible cause:
The circuit is
faulty.
Measure: Send the
device to the
maintenance
center.
Possible cause: The
circuit is faulty.
Measure: Send the
device to the
maintenance
center.
● Possible cause:
The transient
load power is
too high.
Measure: Locate
the load and
remove it.
● Possible cause:
The circuit is
faulty.
Measure: Send the
device to the
maintenance
center.
72