Cold-Starting The Upss Using Batteries - Huawei UPS2000-G-6KRTLL User Manual

Hide thumbs Also See for UPS2000-G-6KRTLL:
Table of Contents

Advertisement

UPS2000-G-6KRTLL
User Manual
Figure 5-9 Password setting screen
Step 3 Operate the UPSs one by one to set the number of parallel output UPSs. Press
SELECT, go to the setting screen, and set parallel system parameters. Press ON/
MUTE+SELECT to return to the standby screen.
Number of Parallel UPSs
Step 4 Perform the startup operation on each UPS. The UPS parallel system transfers to
normal mode.
Step 5 After checking that the system runs properly, switch on the general output circuit
breaker Q and branch output circuit breakers for the parallel system to start loads
one by one.
----End

5.3.1.2 Cold-Starting the UPSs Using Batteries

Step 1 Switch on the external battery circuit breaker (if any).
Step 2 Switch on the AC output circuit breakers Q1 and Q2 for the UPS system.
Step 3 Press ON/MUTE to start the UPSs. The UPSs will enter the standby mode. Press
and hold SELECT for 1s on a non-setting screen to access the login screen for
Issue 01 (2020-08-06)
Copyright © Huawei Technologies Co., Ltd.
Description
● Default value: 1
● Value range: 1–4
5 Operations
82

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents