Huawei UPS2000-G-6KRTLL User Manual page 66

Hide thumbs Also See for UPS2000-G-6KRTLL:
Table of Contents

Advertisement

UPS2000-G-6KRTLL
User Manual
Alarm
Alarm
ID
Name
08
High bus
voltage
09
Bus
short-
circuit
Issue 01 (2020-08-06)
Severity
Clearance
Condition
Critical
When the
bus
voltage is
lower
than 360
V, the
alarm can
be
automatic
ally
cleared
for two
times.
After that,
you need
to
manually
clear the
fault or
power off
and
restart
the
device.
Critical
You need
to
manually
rectify the
fault or
power off
and
restart
the
device.
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on the
Condition
System
The bus
The system
voltage is
shuts down the
greater than
inverter and
450 V for
transfers to
200 ms or
bypass mode.
greater than
470 V for 1
ms.
The bus soft-
The system
start time
cannot start
exceeds 15s.
inverter output
and transfers
to bypass
mode.
4 Control Panel
Suggestion
● Possible cause:
Power grid surge
occurs.
Measure: Improve
the power grid
quality.
● Possible cause:
The parallel
cable is
disconnected
when UPSs are
connected in
parallel.
Measure: Check
that the parallel
cable and current
equalization cable
are properly
connected.
● Possible cause:
The circuit is
faulty.
Measure: Send the
device to the
maintenance
center.
Possible cause: The
circuit is faulty.
Measure: Send the
device to the
maintenance
center.
60