Huawei UPS2000-G-6KRTLL User Manual page 77

Hide thumbs Also See for UPS2000-G-6KRTLL:
Table of Contents

Advertisement

UPS2000-G-6KRTLL
User Manual
Alarm
Alarm
ID
Name
51
Output
overcurre
nt
52
Bus
undervol
tage
53
Timeout
in
approach
ing rated
output
voltage
during
startup
Issue 01 (2020-08-06)
Severity
Clearance
Condition
Critical
You need
to
manually
rectify the
fault or
power off
and
restart
the
device.
Critical
You need
to
manually
rectify the
fault or
power off
and
restart
the
device.
Critical
You need
to
manually
rectify the
fault or
power off
and
restart
the
device.
Copyright © Huawei Technologies Co., Ltd.
Trigger
Impact on the
Condition
System
The output
The system
current
shuts down the
exceeds 80 A
inverter and
for 1 ms.
transfers to
bypass mode.
● Battery
The system
mode: The
shuts down the
bus
inverter and
voltage is
transfers to
over 100
bypass mode.
V less
than 7
times the
battery
voltage.
● Normal
mode: The
bus
voltage is
over 80 V
less than
the peak
mains
voltage.
The inverter
The system
voltage is
shuts down the
not soft-
inverter and
started to
transfers to
the rated
bypass mode.
output
voltage
within 10s.
4 Control Panel
Suggestion
● Possible cause:
The transient
load power is
too high.
Measure: Locate
the load and
remove it.
● Possible cause:
The circuit is
faulty.
Measure: Send the
device to the
maintenance
center.
● Possible cause:
The transient
load power is
too high.
Measure: Locate
the load and
remove it.
● Possible cause:
The circuit is
faulty.
Measure: Send the
device to the
maintenance
center.
Possible cause: The
circuit is faulty.
Measure: Send the
device to the
maintenance
center.
71