Above ground power preparation

If power via conduit is being supplied to the Ultra 50 above
ground, the conduit will enter the Ultra 50 via the back radiator
panel on the left-hand side, as shown in Figure 6.
Use the Ultra 50 template (supplied in the crate kit), or measure
as per Figure 5, to ensure the fixing points are correct. Locate
mounting studs and conduit within 0.05" (1.25mm) tolerance.
To ensure the correct seal is maintained into the Ultra 50, only
use Flexa 1-1/4 inch ROHRflex conduit, order code 0237.202.036
(not supplied) to bring power cabling into the Ultra 50.
Figure 6
Leave at least 1 meter/3 feet of power cabling from the back-left
fixing point, for installation as shown in Figure 7.
Prior to installation the conduit and wiring will require
trimming.
Installation Manual
Back
left
fixing
point
Figure 7
Fixing points.
Use 4 x 5/8-11 studs, protruding 1.2-1.6 inches above the
surface. If the studs protrude more than this it will be
impossible to remove and replace the radiator, if required.
Ethernet cable hole:
If hardwiring in the Ethernet, use the hole referenced in
Figure 5.
| VersiCharge Ultra 50™
Top view
1 meter/3 feet
Not to scale
13