Closing checklist
• Place the radiator onto the fixing studs.
• Fasten the radiator onto the studs with the supplied nuts
using an 8mm socket.
5. Replace cap on Ethernet port
6. Attach front/rear radiator panels
Sit the radiator panel on the base and against the metalwork,
lining up the plastic holes with the bracket nutserts. Fasten with
nylon washers and security screws using the 5mm Pin Hex tool.
Do not over tighten.
If the power is above ground, the rear radiator panel provides
the exit point for the conduit from the Ultra 50.
Cut the four tabs on the lower, right hand of the radiator
panel to remove the material to open the conduit exit point.
Installation Manual
TAB 2
TAB 1
Replace the rear radiator panel ensuring the conduit is fitted
securely within this exit area.
If there are more than two conduit hoses (possible Ethernet
cable in conduit) place the largest at the base with the smaller
feeding above.
| VersiCharge Ultra 50™
TAB 3
TAB 4
27