SmartACU2000B smart array controller
User Manual (with PID modules, 800 V AC)
Locati
Component
on
switching
Box-ty
MCB
pe
transfo
rmer
Three-pha
se power
switch
Issue 05 (2019-01-20)
Recommended Model or
Specifications
Optical
PLCLC5S-ST3P302-HW,
jumper
LC-LC-S2-L2,
3ECA1031LCLC002-01-F, or
LP-LP-2S-P-SM-002
Recommended rated current: 32 A;
number of poles: 2
Knife fuse
When the rated AC voltage on the
switch
low-voltage side of the box-type
(solution 1)
transformer is less than or equal to
500 V, the rated voltage of the knife
fuse switch should be greater than or
equal to 600 V.
When the rated AC voltage on the
low-voltage side of the box-type
transformer is greater than 500 V and
less than or equal to 800 V, the rated
voltage of the knife fuse switch
should be greater than or equal to
800 V.
Recommended rated current of the
fuse: 32 A; rated current of the knife
fuse switch box ≥ 32 A; number of
poles: 3 (3 fuses for each knife fuse
switch box)
MCCB
When the rated AC voltage on the
(solution 2)
low-voltage side of the box-type
transformer is less than or equal to
500 V, the rated voltage of the
molded case circuit breaker (MCCB)
should be greater than or equal to
600 V.
When the rated AC voltage on the
low-voltage side of the box-type
transformer is greater than 500 V and
less than or equal to 800 V, the rated
voltage of the MCCB should be
greater than or equal to 800 V.
Let-through energy ≤ 1.26 x 10
Recommended rated current: 32 A;
number of poles: 3
Copyright © Huawei Technologies Co., Ltd.
Source of
Quantity
Compon
ent
8
Prepared
1
by the
customer
Prepared
by the
customer
Prepared
by the
customer
6
2
A
s
2 Overview
Scenario
with a
double-colu
mn
transformer:
1
Scenario
with a
dual-split
transformer:
2
24