SmartACU2000B smart array controller
User Manual (with PID modules, 800 V AC)
Table 2-4 Components and reserved installation positions
Part No.
Name
1
Functional earthing bar
2
24 V DC power module
(left figure)
Power adapter (right
figure)
3
PID01 input switch
4
PID02 input switch
5
Single-phase SPD
6
Three-phase SPD 1
7
Three-phase SPD 2
8
Position for the LAN
switch
9
PLC CCO
Issue 05 (2019-01-20)
Specifications
N/A
AC input: 100–240 V, 50 Hz/60
Hz
DC output: 12 V DC, 60 W
(maximum); 24 V DC, 30 W
(Maximum)
NOTE
If an external 24–28 V DC input is used,
the DC output voltage ranges from 21.5
V to 25.2 V.
AC input: 100–240 V, 50 Hz/60
Hz
DC output: 12 V/2 A
AC: 3 A/3 P
AC: 3 A/3 P
Uc = 385 V AC
30 kA/60 kA, 8/20 μs
4 P
NOTE
The single-phase SPD on the specific
model of smart array controller has three
poles.
Uc = 680 V AC
20 kA/40 kA, 8/20 μs
1 P
Uc = 680 V AC
20 kA/40 kA, 8/20 μs
1 P
N/A
PLC CCO01A
Copyright © Huawei Technologies Co., Ltd.
2 Overview
Quantit
Label
y
1
FE01
(PID01
functional
earthing
bar)
FE02
(PID02
functional
earthing
bar)
1
U01
1
QF03
1
QF05
1
F03
4
F01
4
F02
1
SWITCH
1
PLC CCO
14