4. Prepare the cables as illustrated.
-
A in Fig. 7-6 illustrates how cables with an outer cable screen or shield are prepared for EMC
bonding with the metal enclosure of the cabinet.
-
B in Fig. 7-6 illustrates how cables without an outer screen or shield are prepared.
A
1
2
3
4
Figure 7-6: Preparing cables for EMC plates: (A) cables with an outer screen or shield, (B)
cables without an outer screen or shield
(1) Grommet
(2) EMC sleeve
(3) Cable tie
(4) Heat-shrinkable termination
(5) Outer cable sheath
5. Route the equipotential bonding conductor through an unused hole of the entry plate.
Note: If all of the holes are used for conductors, route the equipotential bonding conductor
together with a conductor.
3BHS213401 E01 REV H
5
6
7
8
(6) Entry plate
(7) Conductor insulation removed to expose
cable shield
(8) Cable screen extension to connect to the
PE busbar