5
Figure 9-1: Local operator panel
(1) CDP control panel:
-
Starts and stops the motor
-
Displays status messages
-
Displays alarm and fault messages of the drive
and monitored foreign equipment
-
Resets alarm and fault messages
(2) Main supply off:
-
Illuminated pushbutton opens the main
circuit breaker
(3) Main supply on:
-
Illuminated pushbutton charges the DC link
and closes the main circuit breaker
For more information, see "10 CDP control panel" on page 127.
3BHS213401 E01 REV H
3
(4) Grounding switch unlocked:
-
(5) Emergency-off:
-
-
ACS1000 AIR-COOLED USER MANUAL
Lights up to indicate that the grounding
switch of the drive can be turned to the
grounded or ungrounded position
Latching pushbutton, prevents starting when
pressed at standstill of the drive
Main circuit breaker opens immediately and
DC link discharges when pressed during
operation of the drive