Splitting multi-core cables
This section applies to drives without an additional cabinet.
-
Check the distance between point of cable entry and closest busbar.
-
Check the cable diameter.
-
If distance and cable diameter do not allow bending the cable inside the terminal
compartment, separate the conductors outside of the terminal compartment.
Continue with:
-
"7.5.1.4 Preparing cables for EMC plates" on page 90
-
"7.5.1.5 Preparing cables for cable entries with sealing modules" on page 92
-
"7.5.1.6 Preparing cables for cable entries with cable glands" on page 93
7.5.1.4
Preparing cables for EMC plates
As a standard, the cabinet is delivered for cable entry through the roof of the terminal
compartment. If cables are entered through the floor, swap entry plate and cover plate.
The orientation of the EMC plates is the same for cable entry through the roof and through the
floor, ie, the sealing grommets face upwards.
1. Remove the grommets.
2. To ensure proper sealing, cut along the marking that corresponds to the cable diameter.
Slide the grommet onto the cable.
Note: The grommet must fit tightly to prevent water entering the cabinet. The grommets
can be discarded if cables are entered through the floor.
3. If necessary, remove the entry plate and push the cable through the entry holes.
3BHS213401 E01 REV H
ACS1000 AIR-COOLED USER MANUAL
07 ELECTRICAL INSTALLATION
90/184