ABB ACS1000 User Manual page 80

Medium voltage ac drives air-cooled
Hide thumbs Also See for ACS1000:
Table of Contents

Advertisement

6.4
Preparing the floor
Condition of the floor:
-
Must support the weight of the cabinet
-
Overall incline across 5 m must not exceed 5 mm
-
Even
-
Non-flammable, smooth and non- abrasive
-
Protected against humidity diffusion
6.5
Fixing the cabinet to the floor
Important: If the doors of medium voltage compartments cannot be opened,
contact the ABB service organization.
1. Drill fixing holes into the floor as indicated on the layout drawing.
2. When the cabinet is in place, check if the doors are misaligned.
Note: If the doors do not open and close properly, place leveling plates at the appropriate
points (arrows in Fig. 6-1).
-
Recommended size: 80 x 300 x 0.5 mm
Figure 6-1: Leveling the drive
3. Fix the cabinet to the floor.
Note: Floor fixings are not supplied.
-
Anchor bolts as illustrated, or screws and nuts of size M16 are recommended.
-
Insert the screws from the ends of the cabinet base or via the holes inside the cabinet.
3BHS213401 E01 REV H
ACS1000 AIR-COOLED USER MANUAL
06 MECHANICAL INSTALLATION
78/184

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents