1.9.2 DC Link Voltage Control (VdcCtrl Reg - Max Regen Power)

The Function is available only with a Sensorless and Field Oriented regulation mode. The Block allows the
control:
· of the DC link voltage during regenerating (ex. deceleration), to avoid the Overvoltage alarm trip.
or
· the control of the power recovered on the DC link during regenerating.
The two functions are activated by setting the following parameters respectively in the Trq curr lim cfg / Tcrr lim
sel of the Torque Setpoint Block:
T lim Vdc ctrl
T lim gen power
During such phases the VdcCtrl P gain and VdcCtrl I gain parameters (gains) allow the tuning, if required, of
the DC link control.
Description:
TORQUE CONFIG
TORQUE CONFIG
VdcCtrl P gain
VdcCtrl I gain
Max regen power
Ch.1
114
for a control of the DC link voltage
for a control of the recovered power
VdcCtrl reg
>> VdcCtrl P gain
>> VdcCtrl I gain
Max regen power
>> Max regen power
SAVE PARAMETERS
Proportional gain
Integral gain
Regenerating power limit. It is valid in case the Tlim Gen Power mode is active.
—————— Function Description ——————
GEH-6641E
<<
<<
<<